Chapter 12 Description of Parameter SettingsCFP2000
When in fire mode, the drive does not execute over-current stall prevention function. Any
operating over-current stall prevention is automatically invalid when in fire mode.
When in fire mode, over-torque detection function is not available.
When in fire mode, oL1/oL2 detection function is not available.
When in fire mode, abnormal communication (CE10, CE1, CE2, CE3 and CE4) detection is not
available.
The cd1, cd2, cd3 and Hd0, Hd1, Hd2, Hd3 are boot check and cannot be cleared. The above
errors cannot be cleared when in fire mode. The drive does not operate when in fire mode.
Lv protection is not activated when in fire mode, so the drive keeps running or runs until the
power is lost. If the Lv error occurs before the fire mode warning, clear the Lv error to operate the
drive.
If bypass fire mode indication (MOx=54) is activated, reboot the drive and deactivate the fire
mode to turn off this terminal output.
When in fire mode, the output stop function is not available.
When in fire mode, the skip frequency function is not available.
When in fire mode, the operating frequency for Pr.06-81 cannot be larger than Pr.01-00
Maximum Output Frequency. If Pr.06-81 > Pr.01-00, the maximum frequency is automatically set
to Pr.01-00.
12.1-06-31