Chapter 11 Summary of Parameter SettingsCFP2000
Pr.
Parameter Name
06-80
Fire mode
Operating frequency when
 06-81
running fire mode
 06-82
Enable bypass on fire mode
 06-83
Bypass delay time on fire mode
Number of times of reset in fire
 06-84
mode
Length of time of reset in fire
 06-85
mode
06-86
Fire mode motion
 06-87
Fire mode PID set point
Setting Range
0: Disable
1: Operates in counter clockwise direction
2: Operates in clockwise direction
0.00–599.00 Hz
0: Disable bypass
1: Enable bypass
0.0–6550.0 sec.
0–10
0.0–6000.0 sec.
bit0: 0=Open Loop; 1=Close Loop (PID control)
bit1: 0=Manual reset fire mode; 1=Auto reset fire mode
0: Open loop control and manual reset fire mode
1: Close loop control and manual reset fire mode
2: Open loop control and auto reset fire mode
3: Close loop control and auto reset fire mode
0.00–100.00%
11-26
Default
0
60.00
0
0.0
0
60.0
0
0.00