Chapter 12 Description of Parameter SettingsCFP2000
 When set to 6, clear internal PLC program (includes the related settings of PLC internal CANopen
master)
 When set to 7, reset the related settings of CANopen slave.
 When set to 9 or 10, reset all parameters to defaults. If there is a password set in Pr.00-08, enter
the password set in Pr.00-07 to reset to default.
 When it is set to 6, 7, 9 and 10, reboot the motor drive after setting.
Start-up Display Selection
Settings 0: F (Frequency command)
 This parameter determines the start-up display page. This is the user defined choice display
according to the setting in Pr.00-04.
Content of Multi-function Display
Settings 0: Display output current (A) (Unit: Amp)
1: H (Output frequency)
2: U (User defined)
3: A (Output current)
1: Display counter value (c) (Unit: CNT)
2: Display actual output frequency (H) (Unit: Hz)
3: Display DC bus voltage (v) (Unit: V
4: Display output voltage (E) (Unit: V
5: Display output power angle (n) (Unit: deg)
6: Display output power in kW (P) (Unit: kW)
7: Display actual motor speed rpm (Unit: rpm)
10: Display PID feedback (b) (Unit: %)
11: Display AVI1 in % (1.) (Unit: %)
12: Display ACI in % (2.) (Unit: %)
13: Display AVI2 in % (3.) (Unit: %)
14: Display the temperature of IGBT (i.) (Unit:
15: Display the temperature of capacitance (c.) (Unit:
16: The status of digital input (ON/OFF) (i)
17: The status of digital output (ON/OFF) (o)
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital input (d)
20: The corresponding CPU pin status of digital output (0.)
26: Ground Fault GFF (G.) (Unit: %)
27: DC bus voltage ripple (r.) (Unit: V
28: Display PLC register D1043 data (C)
30: Display output of user defined (U)
31: Display Pr.00-05 user Gain (K)
12.1-00-2
Default: 0
Default: 3
)
DC
)
AC
°
C)
°
C)
)
DC