When in fire mode, the running direction of the drive is based on Pr.06-08=1 (FWD) or
Pr.06-80=2 (REV). Other running direction commands are invalid and Pr.00-23 Motor Operating
Direction is not available when in fire mode.
When in fire mode, all keypad command are ignored, including RUN, STOP, JOG and direction
commands.
When in fire mode, all RS-485 communication commands are ignored, including RUN, STOP,
JOG and direction commands.
When in fire mode, B.B. and EF are not activated, including external terminal B.B,
communication B.B, external terminal EF, communication EF and external terminal EF1). Any
activated B.B. is automatically invalid, including external terminal B.B. and communication B.B.,
and the drive executes speed tracking.
When in fire mode, activated EF and EF1 are automatically invalid, including external terminals
EF & EF1 and communication EF).
When in fire mode, the JOG command is not available (JOG command source: keypad, external
terminals and communications). Any operating JOG command is automatically invalid.
When in fire mode, the Acceleration / Deceleration Speed Inhibit function is not available. Any
activated acceleration / deceleration speed inhibition is automatically invalid.
When in fire mode, If you set Pr.06-86 to bit0=0 (open-loop control), the drive does not execute
parameter group 08 PID function. Any operating PID function is automatically invalid.
When in fire mode, the Hand-Off-Auto function is not available, including multi-function output
terminals.
When in fire mode, the drive does not execute the circulative control function, and all circulating
control function parameters are cleared. The circulative control function is automatically invalid
when in fire mode.
When in fire mode, the drive does not execute the sleep function.
When in fire mode, the drive does not execute the DC brake function. Any operating DC brake is
automatically invalid when in fire mode.
Chapter 12 Description of Parameter SettingsCFP2000