Delta CFP2000 Series User Manual page 284

Ip55 fan and pump drive
Table of Contents

Advertisement

Settings
Functions
49
Enable drive
Slave dEb action to
50
execute
Selection for PLC mode
51
bit0
Selection for PLC mode
52
bit1
Trigger CANopen quick
53
stop
UVW output
54
electromagnetic valve
switch
55
Brake release
LOCAL / REMOTE
56
Selection
Enable fire mode with
58
RUN Command
Enable fire mode
59
without RUN Command
60
Disable all the motors
61
Disable Motor 1
62
Disable Motor 2
63
Disable Motor 3
64
Disable Motor 4
65
Disable Motor 5
66
Disable Motor 6
67
Disable Motor 7
Chapter 12 Description of Parameter SettingsCFP2000
When the drive is enabled, the RUN command is valid.
When the drive is disabled, the RUN command is invalid.
When drive is operating, the motor coasts to stop.
This function varies with MOx=45.
Enter the message setting in this parameter when the master
triggers dEb. This prevents over-low voltage of the slave DC bus,
causes the Lv error occurs and the drive coasts to stop.
PLC status
Disable PLC function (PLC 0)
Trigger PLC to operation (PLC 1)
Trigger PLC to stop (PLC 2)
No function
When this function is enabled under CANopen control, it changes
to Quick Stop. Refer to Section 15 CANopen Overview for more
details.
Allows receiving confirmation signals while there is UVW magnetic
contactor during output.
When Pr.02-56 ≠ 0, connect the brake release signal to
multi-function input terminals. When the brake is opened, and the
drive does not receive its confirming signal, the Brk error occurs.
Use Pr.00-29 to select for LOCAL / REMOTE mode (refer to
Pr.00-29). When Pr.00-29 is not set to 0, the digital keypad
KPC-CC01 displays the LOC / REM status. (KPC-CC01 firmware
version 1.021 and above).
REM
LOC
Enable this function under fire mode to force the drive to run (while
there is RUN command).
Enable this function under fire mode to force the drive to run (while
there is not a RUN command).
ON: when the multi-motor circulative control is enable, all motors
coast to stop.
These functions work with multi-motor circulative control, motor 1 to
8 can be set to coast to stop. If any of Auxiliary Motor 1 to Motor 8 is
out of order or under maintenance, enable this terminal to bypass
that motor.
12.1-02-7
Descriptions
bit1
bit 0
0
1
bit0
0
0
0
1
1
0
1
1