Delta CFP2000 Series User Manual page 41

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 2 InstallationCFP2000
2-2 Airflow and Power Dissipation
Model No.
VFD007FP4EA-41/ 52 / 52S
VFD015FP4EA-41/ 52 / 52S
VFD022FP4EA-41/ 52 / 52S
VFD037FP4EA-41/ 52 / 52S
VFD040FP4EA-41/ 52 / 52S
VFD055FP4EA-41/ 52 / 52S
VFD075FP4EA-41/ 52 / 52S
VFD110FP4EA-41/ 52 / 52S
VFD150FP4EA-41/ 52 / 52S
VFD185FP4EA-41/ 52 / 52S
VFD220FP4EA-41/ 52 / 52S
VFD300FP4EA-41/ 52 / 52S
VFD370FP4EA-41/ 52 / 52S
VFD450FP4EA-41/ 52 / 52S
VFD550FP4EA-41/ 52 / 52S
VFD750FP4EA-41/ 52 / 52S
VFD900FP4EA-41/ 52 / 52S
The required airflow shown in the table is for installing single drive
in a confined space.
When installing multiple drives, the required air volume should be
the required air volume for single drive X the number of the drives.
Airflow Rate for Cooling
Flow Rate [cfm]
External
Internal
-
14
-
14
34
14
34
14
34
14
34
14
34
14
88
14
88
14
88
14
88
14
200
29
200
29
285
29
285
29
330
29
330
29
2-4
Power Dissipation for AC Motor Drive
Power Dissipation [watt]
Total
Loss External
14
32
14
43
48
74
48
92
48
113
48
139
48
195
102
240
102
309
102
353
102
449
229
618
229
726
314
864
314
1068
359
1407
359
1623
The heat dissipation shown in the table
is for installing single drive in a confined
space.
When installing multiple drives, volume
of heat dissipation should be the heat
dissipated for single drive X the number
of the drives.
Heat dissipation for each model is
calculated by rated voltage, current and
default carrier.
Internal
Total
20
52
21
64
25
99
26
118
26
139
27
166
29
224
34
274
38
347
39
392
47
496
84
702
87
813
82
946
84
1152
111
1518
114
1737
Table 2-3