ACI Lowest Point
Settings
ACI Proportional Low Point
Settings
ACI Mid-Point
Settings
ACI Proportional Mid-Point
Settings
ACI Highest Point
Settings
ACI Proportional Highest Point
Settings
 When Pr.03-29=1, ACI setting is 0–10 V and the unit is in voltage (V). When Pr.03-29≠1, ACI
setting is 0–20 mA or 4–20 mA, and the unit is in current (mA).
 When you set the analog input ACI to frequency command, 100% corresponds to Fmax
(Pr.01-00 maximum operation frequency).
Pr.03-29=0, 0.00–20.0 mA
Pr.03-29=1, 0.00–10.00 V
Pr.03-29=2, 0.00–20.00 mA
-100.00–100.00%
Pr.03-29=0, 0.00–20.00 mA
Pr.03-29=1, 0.00–10.00 V
Pr.03-29=2, 0.00–20.00 mA
-100.00–100.00%
Pr.03-29=0, 0.00–20.00 mA
Pr.03-29=1, 0.00–10.00 V
Pr.03-29=2, 0.00–20.00 mA
-100.00–100.00%
12.1-03-23
Chapter 12 Description of Parameter SettingsCFP2000
Default:
4.00 / 0.00 / 0.00
Default: 0.00
Default:
12.00 / 5.00 / 10.00
Default: 50.00
Default:
20.00 / 10.00 / 20.00
Default: 100.00