Delta CFP2000 Series User Manual page 399

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
ASCII Mode
Command Message:
STX
ADR 1
ADR 0
CMD 1
CMD 0
Target register
Number of register
(count by word)
Number of register
(count by byte)
The first data content
The second data
content
LRC Check
END
RTU mode:
Command Message:
ADR
CMD
Target register
Number of register
(Count by word)
Quantity of data (byte)
The first data content
The second data
content
CRC Check Low
CRC Check High
Check sum
ASCII mode:
LRC (Longitudinal Redundancy Check) is calculated by summing up the values of the bytes from
ADR1 to last data character then calculating the hexadecimal representation of the
2's-complement negation of the sum.
For example,
01H+03H+21H+02H+00H+02H=29H, the 2's-complement negation of 29H is D7H.
':'
'0'
'1'
'1'
'0'
'0'
'4'
Target register
'0'
'0'
'0'
'0'
Number of register
(count by word)
'0'
'2'
'0'
LRC Check
'4'
'1'
'3'
'8'
'8'
'0'
'F'
'A'
'0'
'9'
'B'
CR
LF
01H
10H
04H
Target register
00H
00H
Number of register
(Count by word)
02H
04
CRC Check Low
13H
CRC Check High
88H
0FH
A0H
'9'
'A'
12.1-09-6
Response Message
STX
ADR 1
ADR 0
CMD 1
CMD 0
END
Response Message:
ADR
CMD 1
':'
'0'
'1'
'1'
'0'
'0'
'4'
'0'
'0'
'0'
'0'
'0'
'2'
'E'
'9'
CR
LF
01H
10H
04H
00H
00H
02H
40H
F8H

Advertisement

Table of Contents
loading

Table of Contents