Chapter 6 Control TerminalsCFP2000
Terminals
MI1
|
Multi-function input 1–8
MI8
DCM
Digital frequency signal common
RA1
Multi-function relay output 1 (N.O.) a
RB1
Multi-function relay output 1 (N.C.) b
RC1
Multi-function relay common
RA2
Multi-function relay output 2 (N.O.) a
RC2
Multi-function relay common
RA3
Multi-function relay output 3 (N.O.) a
RC3
Multi-function relay common
+10V
Potentiometer power supply
Analog voltage input
AVI1
Analog current input
ACI
Terminal Function
Figure 6-19
Figure 6-20
Factory Setting (NPN mode)
Refer to parameters 02-01–02-08 to program the
multi-function inputs MI1–MI8.
Source Mode
ON: the activation voltage
OFF: cut-off current voltage
Sink Mode
ON: the activation voltage
OFF: cut-off current voltage
The internal resistance is 3.6 kΩ.
Digital frequency signal common
Resistive Load:
3A (N.O.) / 3A (N.C.) 250 V
5A (N.O.) / 3A (N.C.) 30 V
Inductive Load (COS 0.4):
1.2A (N.O) / 1.2A (N.C.) 250 V
Various kinds of monitor signals output, e.g. operation,
frequency reached, overload indication, etc.
Resistive Load:
3A (N.O.) / 250 V
AC
5A (N.O.) / 30 V
DC
Inductive Load (COS 0.4):
1.2A (N.O.) / 250 V
AC
Various kinds of monitor signals output, e.g. operation,
frequency reached, overload indication, etc.
Analog frequency setting: +10 V
Impedance: 20 kΩ
Range: 0–20 mA / 4–20 mA / 0–10 V = 0–Max. Output
Frequency (Pr.01-00)
AVI1 switch, default is 0–10 V
Impedance: 250 Ω
Range: 0–20 mA / 4–20 mA / 0–10 V = 0–Max. Output
Frequency (Pr.01-00)
ACI Switch, default is 4–20 mA
6-8
11 V
DC
5 V
DC
13 V
DC
19 V
DC
AC
DC
AC
20 mA
DC