ABB AC500 V3 Hardware Manual page 520

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
Range
Overflow
Value too
high
Normal
range
Value too
low
Underflow
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process voltage
Current consumption
Inrush current from UP (at power up)
520
-10...+10 V
0...20 mA
0 V
0 mA
11.7589 V
23.5178 mA
:
:
10.0004 V
20.0007 mA
10.0000 V
20.0000 mA
:
:
0.0004 V
0.0007 mA
0.0000 V
0.0000 mA
-0.0004 V
0 mA
:
:
-10.0000 V
0 mA
-10.0004 V
0 mA
:
:
-11.7589 V
0 mA
0 V
0 mA
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
Connections
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
From 24 V DC power supply at the termi-
nals UP/L+ and ZP/M of the CPU/communi-
cation interface module
From UP at normal operation
3ADR010278, 3, en_US
4...20 mA
Digital value
Decimal
0 mA
> 32511
22.8142 mA
32511
:
:
20.0006 mA
27649
20.0000 mA
27648
:
:
4.0006 mA
1
4.0000 mA
0
3.9994 mA
-1
0 mA
-6912
0 mA
-27648
0 mA
-27649
:
:
0 mA
-32512
0 mA
< -32512
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0
V (ZP)
24 V DC
5 %
Yes
10 A fast
Yes, per module
Ca. 2 mA
0.15 A + output loads
0.020 A
Hex.
> 7EFF
7EFF
:
6C01
6C00
:
0001
0000
FFFF
E500
9400
93FF
:
8100
< 8100
2
s
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3