8 digital outputs 24 V DC in 1 group (3.0...3.7)
Cam switch functionality
The inputs/outputs are galvanically isolated from the Ethernet network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
1.7.3.1.2
Functionality
Parameter
Interface
Protocol
Power supply
Supply of the electronic circuitry of the I/O
expansion modules attached
Rotary switches
Analog inputs
Analog outputs
Digital inputs
Digital outputs
LED displays
External supply voltage
Effect of incorrect input terminal connection
Required terminal unit
1.7.3.1.3
Connections
The Ethernet communication interface module CI511-ETHCAT is plugged on the I/O terminal
unit TU507-ETH or TU508-ETH. Properly seat the module and press until it locks in place. The
terminal unit is mounted on a DIN rail or with 2 screws plus the additional accessory for wall
mounting (TA526).
The connection of the I/O channels is carried out using the 30 terminals of the I/O terminal unit.
I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8 and 2.8 as well as 1.9, 2.9 and 3.9 are electrically interconnected within the
terminal unit and have always the same assignment, independent of the inserted module:
Terminals 1.8 and 2.8: Process supply voltage UP = +24 V DC
Terminal 3.8: Process supply voltage UP3 = +24 V DC
2022/01/31
For a detailed description of the mounting, disassembly and connection of the
module, please refer to the System Assembly, Construction and Connection
Ä Chapter 2.6 "AC500 (Standard)" on page 971.
chapter
3ADR010278, 3, en_US
Communication interface modules (S500) > EtherCAT
Value
Ethernet
EtherCAT
From the process supply voltage UP
Through the I/O bus interface (I/O bus)
Not used; reserved for future extensions
4 (configurable via software)
2 (configurable via software)
8 (24 V DC; delay time configurable via soft-
ware)
8 (24 V DC, 0.5 A max.)
For system displays, signal states, errors and
power supply
Via terminals ZP, UP and UP3 (process supply
voltage 24 V DC)
Wrong or no signal detected, no damage up to
35 V
TU507 or TU508
Ä Chapter 1.5.1 "TU507-ETH
and TU508-ETH for Ethernet communication
interface modules" on page 122
Device specifications