ABB AC500 V3 Hardware Manual page 30

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
Processor modules > AC500-eCo
Terminal
24
25
Table 13: Assignment of the terminals for PM5032-R-ETH and PM5052-R-ETH:
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
30
Signal
Description
UP
Process supply voltage UP +24 V DC
ZP
Process supply voltage ZP 0 V DC
Signal
Description
COM 0..11
Input common for digital input signals I0 to I11
I0
Digital input signal I0 (max. 5 kHz)
I1
Digital input signal I1 (max. 5 kHz)
I2
Digital input signal I2 (max. 5 kHz)
I3
Digital input signal I3 (max. 5 kHz)
I4
Digital input signal I4
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
I5
Digital input signal I5
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
I6
Digital input signal I6
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
I7
Digital input signal I7
Forward counter (max. 100 kHz), Encoder (max. 200
kHz)
I8
Digital input signal I8
I9
Digital input signal I9
I10
Digital input signal I10
I11
Digital input signal I11
NO0
Normally-open relay contact of the output NO0
NO1
Normally-open relay contact of the output NO1
NO2
Normally-open relay contact of the output NO2
R0..2
Output common for signals NO0 to NO2
NO3
Normally-open relay contact of the output NO3
NO4
Normally-open relay contact of the output NO4
NO5
Normally-open relay contact of the output NO5
R3..5
Output common for signals NO3 to NO5
C12
Digital input/output signal configurable C12
PWM (max. 100 kHz), PTO (max. 200 kHz)
C13
Digital input/output signal configurable C13
PWM (max. 100 kHz), PTO (max. 200 kHz)
UP
Process supply voltage UP +24 V DC
ZP
Process supply voltage ZP 0 V DC
3ADR010278, 3, en_US
2022/01/31