Device specifications
I/O modules > Analog I/O modules
Parameter
Unused inputs
Overvoltage protection
Technical data of the analog inputs, if used as digital inputs
Parameter
Number of channels per module
Distribution of channels into groups
Connections of the channels C0+ to C7+
Reference potential for the inputs
Input signal delay
Indication of the input signals
Input signal voltage
Input current per channel
Input resistance
Technical data of the analog outputs
Parameter
Number of channels per module
Distribution of channels into groups
Channels C0-...C7-
Channels C0+...C7+
Output type
Galvanic isolation
Configurability
Output resistance (load), as current output
Output loadability, as voltage output
Indication of the output signals
Resolution
430
Signal 0
Undefined signal
Signal 1
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
3ADR010278, 3, en_US
Value
Must be configured as "unused".
Yes
Value
Max. 8
1 group of 8 channels
Terminals 3.0 to 3.7
Terminals 1.9 to 4.9 (ZP)
Typ. 8 ms, configurable from 0.1 to 32 ms
1 LED per channel
24 VDC
-30 V...+5 V
+5 V...+13 V
+13 V...+30 V
Typ. 7 mA
Typ. 1.4 mA
Typ. 4.3 mA
< 9 mA
Ca. 3.5 kW
Value
8, all channels for voltage, the first 4 channels
also for current
1 group of 8 channels
Terminals 2.0...2.7
Terminals 3.0...3.7
Bipolar with voltage, unipolar with current
Against internal supply and other modules
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually),
current outputs only channels 0...3
0 W...500 W
Max. ±10 mA
One LED per channel
12 bits (+ sign)
2022/01/31