Device specifications
I/O modules > Digital I/O modules
Technical data
The System Data of AC500-eCo apply
on page 925
Only additional details are therefore documented below.
Parameter
Galvanic isolation
Isolated groups
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Max. power dissipation within the module
Weight
Mounting position
Cooling
Technical data of the digital inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Input voltage range
Input current per channel (typically at 25 °C)
Connections of the channels I0..I7
Connections of the channels I8...I15
Reference potential for the channels I0...I7
Reference potential for the channels I8...I15
Indication of the input signals
Input type according to EN 61131-2
Input signal range
Signal 0 (max.)
Undefined signal
Signal 1 (min.)
Input delay
Signal 0 -> 1
Signal 1 -> 0
Input data length
192
Ä Chapter 2.5.1 "System data AC500-eCo V3"
Value
Yes, between the input groups and the rest of
the module
2 (8 channels per group)
Ca. 10 mA
6 W
Ca. 222 g
Horizontal or vertical
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
3ADR010278, 3, en_US
Value
16 AC inputs (100-240 V AC)
2 (8 channels per group)
0 V AC...264 V AC (47 Hz...63 Hz)
< 3 mA (at 40 V AC)
> 6 mA (at 164 V AC)
> 8 mA (at 240 V AC)
Terminals 1...8
Terminals 10...17
Terminal 9
Terminal 18
1 yellow LED per channel. The LED is on
when the input signal is high (signal 1).
Type 1
40 V AC
40 V AC < U < 79 V AC
79 V AC
Typ. 24 ms
Typ. 24 ms
2 bytes
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents