The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Number of I/O channels per module
Distribution of the channels into groups
Network interface connector
Rated voltage
Max. permitted total current
Grounding
Screw terminals
Spring terminals
Weight
Mounting position
1.5.3.2
Ordering data
Part no.
1SAP 211 400 R0001 TU517, terminal unit, 24 V DC, screw
1SAP 211 200 R0001 TU518, terminal unit, 24 V DC, spring
1SAP 411 200 R0001 TU518-XC, terminal unit, 24 V DC,
1.5.4 TU531 and TU532 for I/O modules
●
TU531, I/O terminal unit, 230 V AC, screw terminals
●
TU532, I/O terminal unit, 230 V AC, spring terminals
●
TU532-XC, I/O terminal unit, 230 V AC, spring terminals, XC version
●
TU532-H, I/O terminal unit, hot swap, 230 V AC, spring terminals
●
TU532-H-XC, I/O terminal unit, hot swap, 230 V AC, spring terminals, XC version
2022/01/31
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
Description
terminals
terminals
spring terminals, XC version
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
3ADR010278, 3, en_US
Terminal units (AC500 standard) > TU531 and TU532 for I/O modules
Value
Max. 24 (depending on the inserted communi-
cation interface module)
3 groups of max. 8 channels each (2.0...2.7,
3.0...3.7, 4.0...4.7), the allocation of the chan-
nels is given by the inserted communication
interface module
10 screw or spring terminals (1.0...1.9)
24 V DC
10 A via the supply terminals (UP, UP3 and
ZP)
Direct connection to the grounded DIN rail or
via the screws with wall mounting
Front terminal, conductor connection vertically
with respect to the printed circuit board
Front terminal, conductor connection vertically
with respect to the printed circuit board
200 g
Horizontal or vertical
Device specifications
Product life cycle phase *)
Active
Active
Active