ABB AC500 V3 Hardware Manual page 578

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Digital/Analog I/O modules
Parameter
Monitoring point of input/output indicator
Galvanic isolation
Technical data of the digital inputs/outputs if used as inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DC16 to DC23
Reference potential for all inputs
Indication of the input signals
Monitoring point of input/output indicator
Input type (according EN 61131-2)
Input delay (0->1 or 1->0)
Input signal voltage
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. cable length
* Due to the direct connection to the output, the demagnetizing varistor is also effective at the
input (see figure) above. This is why the difference between UPx and the input signal must not
exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V.
Consequently, the input voltage must range from -12 V to +30 V when UPx = 24 V and from
-6 V to +30 V when UPx = 30 V.
Technical data of the digital inputs/outputs if used as outputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DC16 to DC23
578
0-Signal
Undefined Signal
1-Signal
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
shielded
unshielded
Value
LED is part of the input circuitry
Yes, per module
Value
8
1 group of 8 channels
Terminals 4.0 to 4.7
Terminals 1.9...4.9 (negative pole of the supply
voltage, signal name ZP)
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
LED is part of the input circuitry
Type 1
Typ. 0.1 ms, configurable from 0.1...32 ms
24 V DC
-3 V...+5 V
> +5 V...< +15 V
+15 V...+30 V
Within -3 V...+5 V
Within +15 V...+30 V
Typ. 5 mA
> 1 mA
> 2 mA
< 8 mA
1000 m
600 m
Value
8
1 group of 8 channels
Terminals 4.0 to 4.7
3ADR010278, 3, en_US
2022/01/31