ABB AC500 V3 Hardware Manual page 450

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
Range
Normal
range
Measured
value too low
Underflow
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process voltage
Current consumption
Inrush current from UP (at power up)
450
Pt100 / Pt
1000
-50...70 °C
:
:
70.0 °C
:
0.1 °C
0.0 °C
-0.1 °C
:
-50.0 °C
-50.1 °C
:
-60.0 °C
< -60.0 °C
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
Connections
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
From UP at normal operation / with outputs
3ADR010278, 3, en_US
Pt100 /
Ni1000
Pt1000
-50...150 °C
-50...400 °C
400.0 °C
:
:
150.0 °C
:
:
:
:
0.1 °C
0.1 °C
0.0 °C
0.0 °C
-0.1 °C
-0.1 °C
:
:
-50.0 °C
-50.0 °C
-50.1 °C
-50.1 °C
:
:
-60.0 °C
-60.0 °C
< -60.0 °C
< -60.0 °C
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for +24
V (UP) as well as 1.9, 2.9, 3.9 and 4.9
for 0 V (ZP)
24 V DC
5 %
Yes
10 A fast
Yes, per module
Ca. 2 mA
0.15 A + output loads
0.050 A
Digital value
Decimal
Hex.
4000
0FA0
1500
05DC
700
02BC
:
:
1
0001
0
0000
-1
FFFF
:
:
-500
FE0C
-501
FE0B
:
:
-600
FDA8
-32768
8000
2