ABB AC500 V3 Hardware Manual page 847

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Name
1
) With a faulty ID, the module reports a "parameter error" and does not perform cyclic process
data transmission.
2
) Counter operating modes
Table 174: Table Error LED / Failsafe function
Setting
On
Off by E4
Off by E3
On + Failsafe
Off by E4 + Failsafe
Off by E3 + Failsafe
*) The parameter Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.
IO-BUS reset
IO-BUS reset after PROFINET reconnection controls the behavior of PROFINET CI modules in
after PROFINET
relation to connected I/O modules (both safety and non-safety I/O modules).
reconnection
IO-BUS reset after PROFINET reconnection = "On" resets and, thus, re-parameterizes
all attached I/O modules. All internal I/O modules states are reset, including the related
diagnosis information.
Note that if the parameter is set to "On" then:
IO-BUS reset after PROFINET reconnection = "Off" will not reset all attached I/O modules. It
will re-parameterize I/O modules only if parameter change is detected during the reconnec-
tion. All internal I/O modules states are not reset, including the related diagnosis informa-
tion.
Note that if the parameter is set to "Off" then:
2022/01/31
Value
On
Ä Chapter 1.6.1.2.9 "Fast counter" on page 349
The bumpless re-start of non-safety I/O modules will not be supported. It means, for
example, that non-safety output channels will go from fail-safe values to "0" values
during the re-connection and re-parameterization time and after that go to new output
values.
Safety I/O modules will be re-parameterized and re-started as newly started modules,
which may not require their PROFIsafe reintegration, depending on safety CPU state, in
the safety application.
The bumpless re-start of non-safety I/O modules is supported (if no parameters are
changed). It means, for example, that non-safety output channels will not go from fail-
safe values to "0" values during the re-connection and re-parameterization time, but
directly from fail-safe values to new output values.
Safety I/O modules will not be re-parameterized (if no parameters are changed). Thus,
they may continue their operation, which may require their PROFIsafe reintegration in
the safety application on the safety CPU, e.g., if PROFIsafe watchdog time for this
safety I/O module has expired. Any reintegration of such safety I/O modules will be
not only application specific but also PROFIsafe specific and depend on the safety I/O
handling in the safety application.
3ADR010278, 3, en_US
Communication interface modules (S500) > PROFINET
Internal value
Internal value,
type
1
BYTE
Description
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode off
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode off
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode off
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe-mode on *)
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe-mode on *)
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe-mode on *)
Device specifications
Default
Off
847