Device specifications
I/O modules > Analog I/O modules
Range
Underflow
Technical data
The System Data of AC500-eCo apply
on page 925
Only additional details are therefore documented below.
Parameter
Process supply voltage UP
Current consumption from 24 V DC power
supply at the terminals UP/L+ and ZP/M of
the CPU/communication interface module
Galvanic isolation
Surge-voltage (max.)
Max. power dissipation within the module
Weight
Mounting position
Cooling
380
-80 mV ... +80
mV
-80 mV
< -90 mV
Connections
Rated value
Current consumption
Inrush current (at power-up)
Max. ripple
Protection against reversed voltage
Rated protection fuse for UP
Isolated groups
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
Type E
Types R, S
-270 ... +1000
-50 ... +1768
°C
°C
< -270.0 °C
< -50.0 °C
Ä Chapter 2.5.1 "System data AC500-eCo V3"
Value
Terminal 19 for UP (+24 V DC) and terminal 20
for ZP (0 V)
24 V DC
0.10 A
0.07 A²s
5 %
Yes
Not necessary
Ca. 5 mA
Yes, between the channels and the rest of the
module
1 (4 channels per group)
35 V DC for 0.5 s
2.6 W
Ca. 120 g
Horizontal or vertical
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Digital value
Decimal
Hex.
-27648
9400
-32768
8000
2022/01/31