The following figure shows the connection of the module:
2022/01/31
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuit and overload.
Never short-circuit or overload the outputs.
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
Never connect voltages > 240 V. All outputs must be supplied from the
same phase.
Use an external 5 A fast protection fuse for the outputs.
NOTICE!
Risk of damaging the PLC modules!
The PLC modules can be damaged by overload.
Make sure that the total current of each output common terminal (R0..7 and
R8..15) does not exceed 10 A.
Never connect total currents > 10 A per group.
If the group fuse protection is not sufficient, then individual fuse protection of the
outputs should be used.
3ADR010278, 3, en_US
Device specifications