ABB AC500 V3 Hardware Manual page 486

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
1
I/O bus
2
Allocation between terminal number and signal name
3
16 yellow LEDs to display the signal states at the analog outputs (O0 - O15)
4
1 green LED to display the state of the process supply voltage UP
5
2 red LEDs to display errors
6
Label
7
Terminal unit
8
DIN rail
Sign for XC version
Intended purpose
The device can be used as a decentralized I/O extension module for S500 communication
iInterface modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs.
Functionality
16 analog outputs in two groups:
Resolution 12 bits plus sign
486
8 channels configurable for voltage or currrent output (O0...O3 / O8...O11)
8 channels for voltage output (O4...O7 / O12...O15)
3ADR010278, 3, en_US