Device specifications
Communication interface modules (S500) > CANopen
5
)
6
)
7
)
1.7.2.3.9
State LEDs
The LEDs are located at the front of the module. There are 2 different groups:
The 5 system LEDs (PWR, CN-RUN, CN-ERR, S-ERR and I/O bus) show the operation
states of the module and display possible errors.
The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process
supply voltage and the states of the inputs and outputs and display possible errors.
States of the 5
LED
system LEDs
PWR/RUN
CN-RUN
CN-ERR
674
The voltage at digital outputs DC0..DC7 and DO0..DO7 has exceeded the
process supply voltage UP3 (see 'Connections'
tions" on page 660). A diagnosis message appears for the whole module.
This message appears if the output of a channel DC0..DC7 or DO0..DO7
should be switched on while an external voltage is connected. In this case
the start-up is disabled while the external voltage is connected. Otherwise, this
could produce reverse voltage flowing from this output to other digital outputs.
This diagnosis message appears for each channel.
Short circuit: After a short circuit has been detected, the output is deactivated
for 100ms. Subsequently, a new start-up will be executed. This diagnosis mes-
sage appears for each channel.
Color
OFF
Green
Process supply
voltage missing
Yellow
---
Green
---
Red
No system error
3ADR010278, 3, en_US
Ä Chapter 1.7.2.3.3 "Connec-
ON
Flashing
Internal supply
Start-up / pre-
voltage OK,
paring communi-
module ready for
cation
communication
with I/O controller
---
---
Device config-
Flashing:
ured, CANopen
CANopen bus in
bus in OPERA-
PRE-OPERA-
TIONAL state
TIONAL state
and cyclic data
and slave is
exchange run-
being configured
ning
Single flash:
CANopen bus in
STOPPED state.
Flickering: Auto-
detect is active
CANopen Bus is
Flashing: Config-
OFF
uration error
Single flash: error
counter overflow
due to too many
error frames
Double flash: A
node-guard or a
heartbeat event
occurred
Flickering: Auto-
detect is active
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents