Device specifications
Communication interface modules (S500) > PROFINET
12 Terminal unit
13 DIN rail
Sign for XC version
1.7.5.2.1
Intended purpose
The PROFINET communication interface modules CI501-PNIO and CI502-PNIO are used
as communication interface modules in PROFINET networks. The network connection is per-
formed by Ethernet cables which are inserted in the RJ45 connectors in the terminal unit. An
Ethernet switch in the communication interface module allows daisy chaining of the network.
For usage in enhanced ambient conditions (e.g. wider temperature and humidity range), a
special XC version of the device is available.
1.7.5.2.2
Functionality
The communication interface module contains 22 I/O channels with the following properties:
4 configurable analog inputs (2-wire / single-ended) or 2 configurable analog inputs (3-wire /
differential) (1.0...1.3)
2 analog outputs (1.5...1.6)
8 digital inputs 24 V DC in 1 group (2.0...2.7)
8 digital outputs 24 V DC, 0.5 A max. in 1 group (3.0...3.7)
The inputs/outputs are galvanically isolated from the PROFINET network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
Parameter
Interface
Protocol
Power supply
Supply of the electronic circuitry of the I/O
expansion modules attached
Rotary switches
LED displays
External supply voltage
Effect of incorrect input terminal connection
Required terminal unit
1.7.5.2.3
Connections
The Ethernet communication interface module CI501-PNIO is plugged on the I/O terminal unit
TU507-ETH or TU508-ETH
nication interface modules" on page 122. Properly seat the module and press until it locks in
place. The terminal unit is mounted on a DIN rail or with 2 screws plus the additional accessory
for wall mounting (TA526
798
Value
Ethernet
PROFINET IO RT
From the process supply voltage UP
Through the I/O bus interface (I/O bus)
For setting the I/O device identifier for configu-
ration purposes (00h to FFh)
For system displays, signal states, errors and
power supply
Via terminals ZP, UP and UP3 (process supply
voltage 24 V DC)
Wrong or no signal detected, no damage up to
35 V
TU507 or TU508
and TU508-ETH for Ethernet communication
interface modules" on page 122
Ä Chapter 1.5.1 "TU507-ETH and TU508-ETH for Ethernet commu-
Ä Chapter 1.8.2.6 "TA526 - Wall mounting accessory" on page 902).
3ADR010278, 3, en_US
Ä Chapter 1.5.1 "TU507-ETH
2022/01/31

Hide quick links: