ABB AC500 V3 Hardware Manual page 593

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Fig. 91: Connection of active-type sensors (voltage) with no galvanically isolated power supply
to the analog inputs
The following measuring ranges can be configured
on page 599
Voltage
Voltage
For a description of the function of the LEDs, please refer to Diagnosis and displays / Displays
Ä Chapter 1.6.3.1.2.8 "State LEDs" on page 606.
To avoid error messages from unused analog input channels, configure them as "unused".
Connection of passive-type analog sensors (Current) to the analog inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
2022/01/31
CAUTION!
Risk of faulty measurements!
The negative pole at the sensors must not have too large a potential difference
with respect to ZP (max. ±1 V within the full signal range).
Make sure that the potential difference never exceeds ±1 V.
Ä Chapter 1.6.3.1.2.9 "Measuring ranges" on page 606:
0 V...10 V
-10 V...+10 V
3ADR010278, 3, en_US
I/O modules > Digital/Analog I/O modules
Ä Chapter 1.6.3.1.2.6 "Parameterization"
1 channel used
1 channel used
Device specifications
593

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents