Parameter
Current consumption
Inrush current from UP (at power up)
Max. power dissipation within the module
Weight (without terminal unit)
Mounting position
Cooling
No effects of
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
multiple over-
protected individually by an external fuse.
loads
Technical data of the digital inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels I0 to I7
Galvanic isolation
Indication of the input signals
Monitoring point of input indicator
Input type acc. to EN 61131-2
Input delay (0->1 or 1->0)
Input signal voltage
2022/01/31
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication inter-
face module
From UP at normal operation / with outputs
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
I/O modules > Digital I/O modules
Value
5 %
Yes
10 A fast
Yes, per module
ca. 2 mA
0.15 A + output loads
2
0.004 A
s
6 W (outputs OFF)
Ca. 300 g
Horizontal or vertical with derating
(output load reduced to 50 % at 40
°C per group)
The natural convection cooling
must not be hindered by cable
ducts or other parts in the switch-
gear cabinet.
Value
8
4 groups of 2 channels each
Ä Chapter 1.6.1.2.8.3 "Connections"
on page 340
2500 V AC from the rest of the module (I/O
bus)
1 yellow LED per channel
The LEDs are only operating if the module is
initialized
LED is controlled by process CPU
Type 2
Typ. 20 ms
230 V AC or 120 V AC
Device specifications
347