Device specifications
Communication interface modules (S500) > PROFINET
Parameter
Bus connection
Switch
Technology
Transfer rate
Transfer method
Ethernet
Expandability
Adjusting elements
Supported protocols
Acyclic services
Supported alarm types
Min. bus cycle
Conformance class
Protective functions (according to
IEC 61131-3)
*) Priorization with the aid of VLAN-ID including priority level
Technical data of the digital inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DI0 to DI7
856
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010278, 3, en_US
Value
2 x RJ45
Integrated
Hilscher NETX 100
10/100 Mbit/s (full-duplex)
According to Ethernet II, IEEE 802.3
100 base-TX, internal switch, 2x RJ45 socket
Max. 10 S500 I/O modules
2 rotary switches for generation of an explicit
name
RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
PNIO read / write sequence (max. 1024 bytes
per telegram)
Process-Alarm service
Process Alarm, Diagnostic Alarm, Return of
SubModule, Plug Alarm, Pull Alarm
1 ms
CC A
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Galvanic isolation from the rest of the module
Value
8
1 group of 8 channels
Terminals 2.0 to 2.7
2022/01/31