Digital configurable input/output unit.
1 sensor supply voltage 24 V DC, 0.5 A, with short circuit and overload protection
24 digital configurable inputs/outputs 24 V DC (C0 to C23) in 1 group (2.0...2.7, 3.0...3.7 and
4.0...4.7), of which each can be used
Optional with fast counter
The configuration is performed by software. The modules are supplied with a process supply
voltage of 24 V DC.
All available inputs/outputs are galvanically isolated from all other circuitry of the module. There
is no potential separation between the channels within the same group.
For use in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
Functionality
Parameter
Fast counter
LED displays
Internal power supply
External power supply
Required terminal unit
Effect of incorrect input terminal connection
The device is plugged on a terminal unit
for I/O modules" on page 126. Position the module properly and press until it locks in place. The
terminal unit is either mounted on a DIN rail or to the wall using 2 screws plus the additional
accessory for wall mounting (TA526
on page 902).
Connections
The connection of the I/O channels is carried out using the 40 terminals of the I/O terminal unit.
I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8 to 4.8 and 1.9 to 4.9 are electrically interconnected within the I/O terminal unit
and always have the same assignment, irrespective of the inserted module:
2022/01/31
as an input,
as a transistor output with short circuit and overload protection, 0.5 A rated current or
as a re-readable output (combined input/output) with the technical data of the digital
inputs and outputs.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
Value
Integrated, many configurable operating
modes (only with AC500)
For signal states, errors and supply voltage
Through the I/O bus interface (I/O bus)
Via the terminals ZP and UP (process voltage
24 V DC)
TU515 or TU516
TU516, TU541 and TU542 for I/O modules"
on page 126
Wrong or no signal detected, no damage up to
35 V
Ä Chapter 1.5.2 "TU515, TU516, TU541 and TU542
Ä Chapter 1.8.2.6 "TA526 - Wall mounting accessory"
Device specifications
I/O modules > Digital I/O modules
Ä Chapter 1.5.2 "TU515,
281

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents