The assignment of the terminals:
Terminal
10
11
12
13
14
15
16
17
18
19
20
The internal power supply voltage for the module's circuitry is carried out via the I/O bus
(provided by a communication interface module or a CPU). Thus, the current consumption from
24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/communication interface
module increases by 5 mA per AO561.
The external power supply connection is carried out via the L+ (+24 V DC) and the M (0 V
DC) terminals. The M terminal is electrically interconnected to the M/ZP terminal of the CPU/
communication interface module.
2022/01/31
Signal
---
---
---
O0U+
O0I+
O1U+
O1I+
O01-
SG
L+
M
NOTICE!
Risk of imprecise and faulty measurements!
Analog signals may be distorted seriously by external electromagnetic influ-
ences.
Use shielded wires when wiring analog signal sources. The cable shield must
be grounded at both ends of the cable. Provide a potential equalisation of a
low resistance to avoid high potential differences between different parts of the
plant.
3ADR010278, 3, en_US
−−−
10
−−−
11
−−−
12
+
O0U+ 13
O0I+ 14
+
O1U+ 15
O1I+ 16
O01− 17
SG
18
L+
19
M
20
Description
Reserved
Reserved
Reserved
Voltage output of channel 0
Current output of channel 0
Voltage output of channel 1
Current output of channel 1
Negative pole of channels O0 and O1
Shield grounding
Process voltage L+ (24 V DC)
Process voltage M (0 V DC)