ABB AC500 V3 Hardware Manual page 622

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
Communication interface modules (S500) > CANopen
Parameter
Max. power dissipation within the module
Reference potential for all digital inputs and
outputs
Setting of the CANopen Node ID identifier
Mounting position
Cooling
Effect of incorrect input terminal connection
Required terminal unit
622
Current consumption via UP (normal
operation)
Current consumption via UP3
Connections
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
Value
0.2 A
0.06 A + 0.5 A max. per output
Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
6 W
Negative pole of the supply voltage, signal
name ZP
With 2 rotary switches at the front side of the
module
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Wrong or no signal detected, no damage up to
35 V
TU509, TU510, TU517 or TU518
Ä Chapter 1.5.3 "TU517 and TU518 for com-
munication interface modules" on page 132
2022/01/31