Device specifications
I/O modules > Analog I/O modules
The module provides several diagnosis functions
on page 388.
The following figures show the connection of analog actuators to the analog output module
AO561.
U
U
24 VDC
Connection of analog voltage actuators
386
NOTICE!
Risk of damaging the PLC modules!
The PLC modules must not be removed while the plant is connected to a power
supply.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove or replace a module.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
10
---
11
---
12 ---
13 O0U+
14 O0I+
15 O1U+
16 O1I+
17 O01-
18 SG
+
19 L+
-
20 M
The output signal is undefined if the supply voltage at the L+ terminal is below
10 V. This can, for example, occur if the supply voltage has a slow ramp-up /
ramp-down behavior and must be foreseen when planning the installation.
If the output is configured in current mode, the voltage output signal is unde-
fined and must not be connected.
If the output is configured in voltage mode, the current output signal is unde-
fined and must not be connected.
3ADR010278, 3, en_US
Ä Chapter 1.6.2.1.4.6 "Diagnosis"
I
I
+
24 VDC
-
Connection of analog current actuators
10
---
11
---
12 ---
13 O0U+
14 O0I+
15 O1U+
16 O1I+
17 O01-
18 SG
19 L+
20 M
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents