ABB AC500 V3 Hardware Manual page 576

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Digital/Analog I/O modules
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process supply voltage
Connections
Protection against reverse voltage
Rated protection fuse at UP
Rated value
Max. ripple
Current consumption
From UP
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Inrush current from UP (at power-up)
Galvanic isolation
Max. power dissipation within the module
Weight (without terminal unit)
Mounting position
Cooling
576
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010278, 3, en_US
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V
DC)
yes
10 A fast
24 V DC
5 %
0.07 A + max. 0.5 A per output
ca. 2 mA
2
0.04 A
s
Yes, per module
6 W (outputs unloaded)
ca. 125 g
Horizontal mounting or vertical with
derating (output load reduced to 50 % at
40 °C)
The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents