ABB AC500 V3 Hardware Manual page 190

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Digital I/O modules
Hence, replacing I/O modules is possible without any re-parameterization via software.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Param-
eter
name
Module ID Internal
Ignore
module
Parameter
length
Input
delay
1
) With CS31 and addresses less than 70, the value is increased by 1.
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n).
GSD file:
Ext_Module_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
190
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Value
Internal
value
1
6160
)
No
0
Yes
1
Internal
3
20 ms
0
100 ms
1
3ADR010278, 3, en_US
Data type
Default
of
value
internal
value
WORD
6160
0x1810
BYTE
No
0x00
BYTE
3
BYTE
20 ms
0x00
7
0x18, 0x11, 0x00, 0x03, 0x00, 0x00, 0x00;
Min.
Max.
0
65535
-
-
0
255
0
1
EDS Slot
Index
2
xx01
)
-
xx02
2
)
-
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents