State LEDs
LED
Technical data
The System Data of AC500-eCo apply
on page 925
Only additional details are therefore documented below.
Parameter
Process supply voltage L+
2022/01/31
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
With "Device" the following allocation applies:
31 = Module itself,
1...10 = decentralized communication interface module 1...10,
ADR = hardware address (e. g. of the DC551-CS31)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = Module itself; COM1/COM2: 1...10 = expansion
1...10
Channel error: I/O bus or PNIO = Module type (2 = DO); COM1/COM2: 1...10 =
expansion 1...10
In case of module errors, with channel "31 = module itself" is output.
Inputs I0...I7
Outputs
NO0...NO7
In the undefined signal range, the state LED for the inputs can be ON although
the input state detected by the module is OFF.
Connections
Rated value
Current consumption via L+
Inrush current (at power-up)
Max. ripple
Protection against reversed voltage
Rated protection fuse for L+
3ADR010278, 3, en_US
State
Color
Digital input
Yellow
Digital output Yellow
Ä Chapter 2.5.1 "System data AC500-eCo V3"
Value
Terminal 20 for L+ (+24 V DC). The neg-
ative pole is provided by the I/O bus.
24 V DC
50 mA
0.0035 A²s
5 %
Yes
Recommended; the outputs must be pro-
tected by a 3 A fast-acting fuse
Device specifications
I/O modules > Digital I/O modules
LED = OFF
LED = ON
Input is OFF Input is ON
Output is
Output is ON
OFF
265