System assembly, construction and connection
AC500 (Standard) > Connection and wiring
Parameter
Type
Degree of protection
Stripped conductor end
Needed tool
Dimensions
Number of cores per terminal
1
1
1 with wire-end ferrule
2
2
2 with TWIN wire end ferrule (length
10 mm) with plastic sleeve
2.6.4.4
Connection of wires at the spring terminals
Connection
Opening
Opening for
for
conductor
Terminal
closed
1
Fig. 190: Connect the wire to the spring terminal (steps 1 to 3)
992
screw-
driver
Screwdriver
b
Spring
a
3ADR010278, 3, en_US
Value
Front terminal
IP 20
9 mm, min. 8 mm
Slotted screwdriver
2.5 x 0.4 to 3.5 x 0.5 mm, screwdriver must be at least 15 mm
free of insulation at the tip
Conductor type
Solid
Flexible
Flexible
Solid
Flexible
Flexible
Terminal
open
2
Cross section
0.08 mm² to 2.5 mm²
0.08 mm² to 2.5 mm²
0.25 mm² to 1.5 mm²
Not intended
Not intended
2 x 0.25 mm² or 2 x 0.5 mm² or
2 x 0.75 mm², with square cross-
section of the wire-end ferrule also
2 x 1.0 mm²
b
Screwdriver
inserted
Screwdriver
a
3
2022/01/31