Device specifications
I/O modules > Digital I/O modules
Parameter
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
Current consumption
From 24 V DC power supply at the ter-
minals UP/L+ and ZP/M of the CPU/com-
munication interface module
From UP at normal operation / with out-
puts
Inrush current from UP (at power up)
Max. power dissipation within the module
Weight (without terminal unit)
Mounting position
Cooling
Technical data of the digital inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels I0 to I7
Terminals of the channels I8 to I15
Reference potential for all inputs
Galvanic isolation
Indication of the input signals
298
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010278, 3, en_US
Value
24 V DC
5 %
Yes
10 A fast
Yes, per module
Ca. 2 mA
0.15 A + max. 0.5 A per output
0.007 A²s
6 W (outputs unloaded)
ca. 125 g
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Value
16
1 group of 16 channels
1.0 to 1.7
2.0 to 2.7
Terminals 1.9, 2.8, 3.8 and 4.9 (negative pole of
the process supply voltage, signal name ZP)
From the rest of the module (I/O bus)
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)