Table 136: Settings "Error LED / Failsafe function"
Setting
On
Off by E4
Off by E3
On +Failsafe
Off by E4 + Failsafe
Off by E3 + Failsafe
*) The parameters Behaviour analog outputs at communication error and Behaviour digital
outputs at communication error are only evaluated if the failsafe function is enabled.
Group parameters for the analog part
Name
Analog data
format
Behavior analog
outputs at com-
munication error
*)
*) The parameter Behavior analog outputs at communication error is only analyzed if the
failsafe mode is ON.
Channel parameters for the analog inputs (4x)
Name
Input 0, Channel
configuration
Input 0, Check
channel
:
:
2022/01/31
Description
Error LED (S-ERR) lights up at errors of all error classes, failsafe
mode off
Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3,
failsafe mode off
Error LED (S-ERR) lights up at errors of error classes E1 and E2,
failsafe mode off
Error LED (S-ERR) lights up at errors of all error classes, failsafe
mode on *)
Error LED (S-ERR) lights up at errors of error classes E1, E2 and E3,
failsafe mode on *)
Error LED (S-ERR) lights up at errors of error classes E1 and E2,
failsafe mode on *)
Value
Internal value
Standard
0
Reserved
255
Off
0
Last value
1
Last value 5 s
6
Last value 10 s
11
Substitute value
2
Substitute value
7
5 s
12
Substitute value
10 s
Value
Internal value
Operation modes
Operation modes
of analog inputs
of analog inputs
Settings channel
Settings channel
monitoring
monitoring
:
:
:
:
3ADR010278, 3, en_US
Communication interface modules (S500) > CANopen
Internal value,
type
BYTE
BYTE
Internal value,
type
BYTE
BYTE
:
:
Device specifications
Default
0
0
Default
0
0
:
: