Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Technical data of the module
Parameter
Process supply voltages UP/UP3
Max. power dissipation within the module
Number of digital inputs
Number of digital outputs
Number of configurable digital inputs/outputs 8
Input data length
Output data length
Reference potential for all digital inputs and
outputs
Setting of the I/O device identifier
Diagnosis
Operation and error displays
Weight (without terminal unit)
Mounting position
Extended ambient temperature (XC version)
Cooling
2022/01/31
Rated value
Max. load for the terminals
Protection against reversed voltage
Rated protection fuse on UP/UP3
Galvanic isolation
Inrush current from UP (at power up)
Current consumption via UP (normal
operation)
Current consumption via UP3
Connections
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
Communication interface modules (S500) > PROFINET
Value
24 V DC (for inputs and outputs)
10 A
Yes
10 A fast
Ethernet interface against the rest of the
module
On request
0.15 A
0.06 A + 0.5 A max. per output
Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
6 W
8
8
12 bytes
20 bytes
Negative pole of the supply voltage, signal
name ZP
With 2 rotary switches at the front side of the
module
See Diagnosis and Displays
1.7.5.3.8 "Diagnosis" on page 848
34 LEDs (totally)
Ca. 125 g
Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
> 60 °C on request
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Device specifications
Ä Chapter