Device specifications
I/O modules > Analog I/O modules
The connection of the I/O channels is carried out using the 40 terminals of the I/O terminal unit.
I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8, 2.8, 3.8 and 4.8 as well as 1.9, 2.9,3.9 and 4.9 are electrically interconnected
within the I/O terminal units and always have the same assignment, independent of the inserted
module:
Terminals 1.8, 2.8, 3.8 and 4.8: process voltage UP = +24 V DC
Terminals 1.9, 2.9, 3.9 and 4.9: process voltage ZP = 0 V DC
The assignment of the other terminals:
Terminals
1.0 to 1.7
2.0 to 2.7
3.0 to 3.7
4.0 to 4.7
The internal power supply voltage for the module's circuitry is carried out via the I/O bus
(provided by a communication interface module or a CPU). Thus, the current consumption from
24 V DC power supply at the terminals L+/UP and M/ZP of the CPU/communication interface
module increases by 2 mA per I/O module.
526
Signal
I0- to I7-
I0+ to I7+
O0- to O7-
O0+ to O7+
The negative poles of the analog inputs are connected to each other to form an
"Analog Ground" signal for the module.
The negative poles of the analog outputs are connected to each other to form
an "Analog Ground" signal for the module.
There is no galvanic isolation between the analog circuitry and ZP/UP. There-
fore, the analog sensors must be galvanically isolated in order to avoid loops via
the ground potential or the supply voltage.
Because of their common reference potential, analog current inputs cannot
be circuited in series, neither within the module nor with channels of other
modules.
For the open-circuit detection (cut wire), each analog input channel is pulled up
to "plus" by a high-resistance resistor. If nothing is connected, the maximum
voltage will be read in then.
3ADR010278, 3, en_US
Description
Negative poles of the 8 analog
inputs
Positive poles of the 8 analog
inputs
Negative poles of the 8 analog
outputs
Positive poles of the 8 analog
outputs