Mounting And Demounting - ABB AC500 V3 Hardware Manual

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

2.6.3 Mounting and demounting

The control system is designed to be mounted to a well-grounded mounting surface such as a
metal panel. Additional grounding connections from the mounting tabs or DIN rail (if used), are
not required unless the mounting surface cannot be grounded.
2.6.3.1
Mounting/Demounting terminal bases and function module terminal bases
Demounting on
DIN rail
1.
2.
2022/01/31
During panel or DIN rail mounting of all devices, be sure that all debris (metal
chips, wire strands, etc.) is kept from falling into the controller. Debris that falls
into the controller could cause damage while the controller is energized.
All devices are grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate stell DIN rail to assure proper grounding. The use of
other DIN rail materials (e.g. aluminium, plastic, etc.) that can corrode, oxidize,
or are poor conductors, can result in improper or intermittent grounding.
Mount DIN rail 7.5 mm or 15 mm.
Mount the terminal base/function module terminal base:
ð The terminal base is put on the DIN rail above and then snapped-in below.
3ADR010278, 3, en_US
System assembly, construction and connection
AC500 (Standard) > Mounting and demounting
981

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents