Technical data of the configurable digital inputs/outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is
done by interrogating or allocating the corresponding channel.
Parameter
Number of channels per module
Distribution of the channels into groups
If the channels are used as inputs
If the channels are used as outputs
Indication of the input/output signals
Galvanic isolation
Technical data of the digital inputs/outputs if used as inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DC0 to DC7
Reference potential for all inputs
Indication of the input signals
Input type (according EN 61131-2)
Input delay (0->1 or 1->0)
Input signal voltage
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. cable length
2022/01/31
Channels DC0...DC07
Channels DC0...DC07
0-Signal
Undefined Signal
1-Signal
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
3ADR010278, 3, en_US
Communication interface modules (S500) > EtherCAT
Value
8 inputs/outputs (with transistors)
1 group for 8 channels
Terminals 1.0...1.7
Terminals 1.0...1.7
1 yellow LED per channel, the LED is ON when
the input/output signal is high (signal 1)
From the Ethernet network
Value
8
1 group of 8 channels
Terminals 1.0 to 1.7
Terminals 1.9...3.9 (negative pole of the supply
voltage, signal name ZP)
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Type 1
Typ. 0.1 ms, configurable from 0.1...32 ms
24 V DC
-3 V...+5 V *)
> +5 V...< +15 V
+15 V...+30 V
Within -3 V...+5 V *)
Within +15 V...+30 V
Typ. 5 mA
> 1 mA
> 2 mA
< 8 mA
1000 m
600 m
Device specifications
727