Parameterization
Firmware version
Firmware version > V2.0.0
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name
Module ID Internal
Ignore
module
2
)
Parameter
length
Check
supply
Input
delay
Behaviour
of outputs
at com-
munica-
tion errors
Substitute
value at
outputs
Bit 3 =
Output 3
Bit 0 =
Output 0
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
2022/01/31
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Value
Internal
value
1205
1
)
No
0
Yes
1
Internal
4
Off
0
on
1
20 ms
0
100 ms
1
Off
0
Last value
1+(n*5)
Substitute
2+(n*5),
value
n £ 2
0...15
0...
0x0f
3ADR010278, 3, en_US
Configuration
The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
Internal
Default
value,
type
Word
1205
0x04B5
Byte
No
0x00
Byte
4-CPU
4-FBP
Byte
On
0x01
Byte
20 ms
0x00
Byte
Off
0x00
Byte
0
0x00
Device specifications
I/O modules > Digital I/O modules
Min.
Max.
0
65535
0
255
0
1
0
1
0
2
0
15
EDS
Slot/
Index
0x0Y01
not for
FBP
0x0Y02
0x0Y03
0x0Y04
0x0Y05
0x0Y06
345