ABB AC500 V3 Hardware Manual page 370

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
Parameter
Galvanic isolation
Input ranges
Indication of the input signals
Module update time
Channel input resistance
Input filter attenuation
Conversion error of the analog values
caused by non-linearity, adjustment
error at factory and resolution within
the normal range
Measuring range
Analog to digital conversion time
Unused inputs
Input data length
Power dissipation inside the sensor
(max.)
Suppression of interference
Maximum input voltage
Basic error (resistance)
Repeatability
Overvoltage protection
Wire loop resistance
Max. cable length (conductor cross
section > 0.14 mm²)
Ordering data
Part no.
1TNE 968 902 R1102 AI562, analog input module, 2 AI, RTD Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
370
Unshielded wire
Shielded wire
Description
screw front, cable side, 6 pieces per
unit
3ADR010278, 3, en_US
Value
Against internal power supply and other modules
Pt100, Pt1000, Ni100, Ni1000
150 W, 300 W
No
All channels: < 1 s
> 100 kW
-3 dB at 3.6 kHz
Typ.
Depending on RTD max. ±0.6 % of full scale
(guaranteed for 3-wires connection only)
at 25 °C
Max.
±2 % of full scale (guaranteed for 3-wires
connection only)
at 0 °C...60 °C or EMC disturbances
Ä Chapter 1.6.2.1.2.8 "Measuring ranges"
on page 367
Typ. 140 ms per channel
Can be left open and should be configured as
"unused"
4 bytes
1 mW
On request
30 V DC (sense), 5 V DC (source)
0.1 % of full-scale
0.05 % of full-scale
Yes, up to 30 V DC
< 20 W
10 m
100 m
Product life cycle phase *)
Active
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents