Device specifications
Communication interface modules (S500) > CANopen
Parameter
Galvanic isolation
Configurability
Output resistance (load), as current output
Output loadability, as voltage output
Indication of the output signals
Resolution
Settling time for full range change (resistive
load, output signal within specified tolerance)
Conversion error of the analog values
caused by non-linearity, adjustment error
at factory and resolution within the normal
range
Relationship between input signal and hex
code
Unused outputs
Technical data of the fast counter
Parameter
Used inputs
Used outputs
Counting frequency
Detailed description
Operating modes
1.7.2.2.12
Ordering data
Part no.
1SAP 228 100
R0001
1SAP 428 100
R0001
656
Bipolar
Description
CI581-CN, CANopen
communication interface module with
8 DI, 8 DO, 4 AI and 2 AO
CI581-CN-XC, CANopen
communication interface module with
8 DI, 8 DO, 4 AI and 2 AO, XC version
3ADR010278, 3, en_US
Value
Voltage
Against internal supply and other modules
-10...+10 V, 0...20 mA, 4...20 mA (each output
can be configured individually)
0...500 W
±10 mA max.
1 LED per channel (brightness depends on the
value of the analog signal)
12 bits (+ sign)
Typ. 5 ms
Typ. 0.5 %, max. 1 %
Ä Chapter 1.7.2.2.10.3 "Output ranges
See
voltage and current" on page 651
Are configured as "unused" (default value) and
can be left open-circuited
Value
Terminal 3.0 (DI0), 3.1 (DI1)
Terminal 4.0 (DO0)
Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Fast Counter
Ä Chapter 1.6.1.2.9 "Fast
counter" on page 349
Operating modes
Ä Chapter 1.6.1.2.9 "Fast
counter" on page 349
Product life cycle phase *)
Active
Active
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3