ABB AC500 V3 Hardware Manual page 393

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

3
Terminal number
4
Allocation of signal name
5
Terminal block for input signals (9-pin)
6
Terminal block for output signals (11-pin)
7
2 holes for wall-mounting with screws
8
DIN rail
Intended purpose
The device can be used as a decentralized I/O extension module for S500 communication
iInterface modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs.
The inputs are not galvanically isolated from each other.
The outputs are not galvanically isolated from each other.
All other circuitry of the module is not galvanically isolated from the inputs/outputs or from the
I/O bus.
Functionality
4 analog inputs, individually configurable for
Not used (default)
-2.5 V...+2.5 V
-5 V...+ 5 V
0 V...+5 V
0 V...+10 V
0 mA...20 mA
4 mA...20 mA
2 analog outputs, individually configurable for
Not used (default)
-10 V...+10 V
0 mA...20 mA
4 mA...20 mA
Parameter
Resolution of the analog channels
Voltage bipolar (-2.5 V...+2.5 V; -5 V...+5 V) 11 bits plus sign
Voltage unipolar (0 V...5 V; 0 V...10 V)
Current (0 mA...20 mA; 4 mA...20 mA)
LED displays
2022/01/31
The I/O module must not be used as a decentralized I/O module with CI590-
CS31-HA communication interface modules.
3ADR010278, 3, en_US
I/O modules > Analog I/O modules
Value
12 bits
12 bits
2 LEDs for process voltage and error mes-
sages
Device specifications
393