Ac500-Xc; System Data Ac500-Xc - ABB AC500 V3 Hardware Manual

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Table 207: Ordering data
Order No.
1SVR360563R1001 CP-C.1
1SVR360663R1001 CP-C.1
1SVR360763R1001 CP-C.1

2.7 AC500-XC

2.7.1 System data AC500-XC

2.7.1.1
Environmental conditions
Table 208: Process and supply voltages
Parameter
24 V DC
120 V AC...240 V AC wide-range supply
Allowed interruptions of power supply
2022/01/31
Type
24/5.0
24/10.0
24/20.0
Assembly, construction and connection of devices of the variant AC500-XC is
identical to AC500 (standard)
The following description provides information on general technical data of
AC500-XC system.
Voltage
Protection against reverse polarity
Voltage
Frequency
DC supply
NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages
could lead to unrecoverable damage of the system. The system might be
destroyed.
NOTICE!
For the supply of the modules, power supply units according to PELV or SELV
specifications must be used.
3ADR010278, 3, en_US
System assembly, construction and connection
Input
Output
110-240 V
24 V DC, 5 A +50 %
AC or
90-300 V DC
110-240 V
24 V DC, 10
AC or
A
90-300 V DC
110-240 V
24 V DC, 20
AC or
A
90-300 V DC
Ä Chapter 2.6 "AC500 (Standard)" on page 971.
Value
24 V (-15 %, +20 %)
Yes
120...240 V (-15 %, +10 %)
50/60 Hz (-6 %, +4 %)
Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC500-XC > System data AC500-XC
Overload
Module
capacity
width [mm]
40
+50 %
60
+30 %
82
1023

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents