ABB AC500 V3 Hardware Manual page 706

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
Communication interface modules (S500) > EtherCAT
Parameter
Transfer method
Ethernet
Expandability (S500 I/O modules)
Indicators
Adjusting elements
Quantity of input/output data
Limit of data for input and output
Acyclic services
Protective functions (according to
CODESYS)
Technical data of the module
Parameter
Process supply voltage UP/UP3
Max. power dissipation within the module
Number of digital inputs
Number of digital outputs
Number of analog inputs
Number of analog outputs
706
Rated value
Max. load for the terminals
Protection against reversed voltage
Rated protection fuse on UP/UP3
Galvanic isolation
Inrush current from UP (at power up)
Current consumption via UP (normal
operation)
Current consumption via UP3
Connections
3ADR010278, 3, en_US
Value
According to Ethernet II, IEEE 802.3
100 base-TX, internal switch, 2x RJ45 socket
Up to 10 S500 I/O modules (Index C0 and
above), not available (Index below C0)
5 LEDs for state indication
2 rotary switches (used for future topology
extensions)
CI512-ETHCAT: 10 bytes input and 14 bytes
output
CI511-ETHCAT: 18 bytes input and 18 bytes
output
144 byte
SDO (1500 bytes max.)
Emergency ECAT_SLV_DIAG
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Galvanic isolation to network
Value
24 V DC (for inputs and outputs)
10 A
Yes
10 A fast
Ethernet interface against the rest of the
module
On request
0.2 A
0.06 A + 0.5 A max. per output
Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
6 W
8
8
4
2
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents