ABB AC500 V3 Hardware Manual page 609

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Parameter
Process supply voltage
Current consumption
Galvanic isolation
Max. power dissipation within the module
Weight (without terminal unit)
Mounting position
Cooling
Technical data of the digital outputs
Parameter
Number of channels per module
Distribution of the channels into groups
Connection of the channels
DO0 to DO7
DO8 to DO15
2022/01/31
Connections
Protection against reverse voltage
Rated protection fuse at UP
Rated value
Max. ripple
From UP
From 24 V DC power supply at the termi-
nals UP/L+ and ZP/M of the CPU/communi-
cation interface module
Inrush current from UP (at power-up)
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010278, 3, en_US
I/O modules > Digital/Analog I/O modules
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0
V)
yes
10 A fast
24 V DC
5 %
0.07 A + max. 0.5 A per output
ca. 2 mA
0.04 A
2
s
Yes, per module
6 W (outputs unloaded)
ca. 125 g
Horizontal mounting or vertical with
derating (output load reduced to 50% at 40
°C)
The natural convection cooling must not be
hindered by cable ducts or other parts in
the switchgear cabinet.
Value
16 outputs (with transistors)
1 group of 16 channels
Terminals 1.0 to 1.7
Terminals 2.0 to 2.7
Device specifications
609

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents