Device specifications
I/O modules > Digital I/O modules
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process supply voltage UP
Connections
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
Current consumption
From 24 V DC power supply at the ter-
minals UP/L+ and ZP/M of the CPU/com-
munication interface module
From UP at normal operation / with out-
puts
Inrush current from UP (at power up)
Max. power dissipation within the module
Weight (without terminal unit)
Mounting position
Cooling
316
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010278, 3, en_US
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP)
as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
24 V DC
5 %
Yes
10 A fast
Yes, per module
Ca. 2 mA
0.10 A + max. 0.5 A per output
2
0.005 A
s
6 W (outputs unloaded)
Ca. 100 g
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.