Parameter
Input delay (0->1 or 1->0)
Input signal voltage
Signal 0
Undefined signal
Signal 1
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. cable length
Technical data of the relay outputs
Parameter
Number of channels per module
Distribution of channels into groups
Connection of the channel R0
Connection of the channel R1
Connection of the channel R6
Connection of the channel R7
Galvanic isolation
Indication of the output signals
Monitoring point of output indicator
Way of operation
Output delay (0->1 or 1->0)
Relay power supply
Relay outputs
Rated protection fuse
Min. switching current
Output switching capacity
2022/01/31
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
Output short circuit protection
Resistive load, max.
Inductive load, max.
Lamp load
3ADR010278, 3, en_US
Value
Typ. 8 ms, configurable from 0.1 to 32 ms
24 V DC
-3 V...+5 V
> +5 V...< +15 V
+15 V...+30 V
Within -3 V...+5 V
Within +15 V...+30 V
Typ. 5 mA
> 1 mA
> 5 mA
< 8 mA
1000 m
600 m
Value
8 relay outputs
8 groups of 1 channel each
Terminal 2.0 (common), 3.0 (NO) and 4.0 (NC)
Terminal 2.1 (common), 3.1 (NO) and 4.1 (NC)
Terminal 2.6 (common), 3.6 (NO) and 4.6 (NC)
Terminal 2.7 (common), 3.7 (NO) and 4.7 (NC)
Between the channels and from the rest of the module
One yellow LED per channel, the LED is ON when the
relay coil is energized
LED is controlled by process CPU
Non-latching type
On request
By UP process supply voltage
Should be provided externally with a fuse or circuit
breaker
6 A gL/gG per channel
10 mA
3 A; 3 A (230 V AC), 2 A (24 V DC)
1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC)
60 W (230 V AC), 10 W (24 V DC)
Device specifications
I/O modules > Digital I/O modules
337