ABB AC500 V3 Hardware Manual page 498

Hide thumbs Also See for AC500 V3:
Table of Contents

Advertisement

Device specifications
I/O modules > Analog I/O modules
Technical data
The system data of AC500 and S500
applicable to the standard version.
The system data of AC500-XC
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Process voltage
Current consumption
Max. length of analog cables, conductor cross sec-
tion > 0.14 mm
Weight
Mounting position
Cooling
498
Connections
Rated value
Max. ripple
Protection against reversed voltage
Rated protection fuse on UP
Galvanic isolation
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Current consumption from UP at normal oper-
ation
Inrush current from UP (at power up)
2
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
3ADR010278, 3, en_US
Ä Chapter 2.6.1 "System data AC500" on page 971 are
Ä Chapter 2.7.1 "System data AC500-XC" on page 1023 are
Value
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for
0 V (ZP)
24 V DC
5 %
Yes
10 A fast
Yes, per module
Ca. 2 mA
0.15 A + output loads
0.040 A
100 m
300 g
Horizontal or vertical with derating
(output load reduced to 50 % at 40 °C
per group)
The natural convection cooling must not
be hindered by cable ducts or other
parts in the switchgear cabinet.
2
s
2022/01/31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac500-eco v3Ac500-xc v3

Table of Contents